Description
Independently monitored data from an innovative ground-coupled heat pump system in a test house is given. Testing was conducted in association with the SERI residential packaged solar heating system program. Innovations included: shallow horizontal slit trenches; multiple small counterflow tubes covered with concrete; two-speed compressor and blower; use of the ground as both heat source and sink; a small-tube vertical heat exchanger serving as both evaporator and condenser; superheat coming only from a suction line heat exchanger; only 110 feet of 4-foot-spaced trenching per ton; elimination of any back-up system; utilization of full night setback ; and packaging of system components. Results fully met expectations with performance far better than air-to-air heat pumps since annual heating/cooling compressor COPs were near 3.5. It is felt this compact horizontal trenching system meets a broad requirement.
Units: I-P
Citation: Symposium, ASHRAE Transactions, 1985, vol. 91, pt. 2B, Honolulu, HI
Product Details
- Published:
- 1985
- Number of Pages:
- 10
- File Size:
- 1 file , 730 KB
- Product Code(s):
- D-HI-85-26-2