Sale!

2901 (RP-188) — Performance of a Two-Phase Thermosiphon Air-to-Air Heat Exchanger

$7.50

Conference Proceeding by ASHRAE, 1985

Category:

Description

The performance of an air-to-air, multiple-loop, two-phase thermosiphon heat exchanger system, utilizing R-11 as its working fluid and finned tube coils as its evaporator and condenser, has been studied experimentally. It was found that the effectiveness of the system was insensitive to the quantity of charge in the evaporator, except when dryout occurred; it increased with the hot to cold air duct temperature difference and decreased as the airflow rates increased.

Units: Dual

 

Citation: ASHRAE Transactions, 1985, vol. 91, pt. 2A, Honolulu, HI

Product Details

Published:
1985
Number of Pages:
7
File Size:
1 file , 1.5 MB
Product Code(s):
D-HI-85-2901