Sale!

CH-99-03-2 (RP-751) — Effects of Oil on Boiling R-123 and R-134a Flowing Normal to an Integral-Finned Tube Bundle

$7.50

Conference Proceeding by ASHRAE, 1999

Category:

Description

Local, experimental heat transfer coefficients have been measured for boiling refrigerant flowing up and across a tube bundle segment representing a full flooded evaporator tube bundle. R-123 and R-134a data with 26 fins per inch (1024 fins per meter) tubes have been obtained. The refrigerant enters at 15% vapor quality and exits at nearly 100% vapor in order to simulate an actual flooded evaporator bundle. The nominal area heat flux was varied from 2,607 to 10,427 Btu/h·ft2 (8,224 to 32,893 W/m2 ) as the tube bundle oil content ranged from 0 to 15% (by weight) for each refrigerant/tube combination. The performance of R-22 without oil has also been determined. Local tube and bulk fluid temperatures were measured directly by thermocouples to calculate the refrigerant-side heat transfer coefficients. The bundle segment saturation temperature set point (taken at the top of the tube bundle) is 40°F (4.4°C).

Units: Dual

Citation: Symposium, ASHRAE Transactions, vol. 105, pt. 1

Product Details

Published:
1999
Number of Pages:
11
File Size:
1 file , 490 KB
Product Code(s):
D-7562