PH-97-10-1 — System Performance of a Split-Type Unit Having R-22 and R-407C as Working Fluids

$7.50

Conference Proceeding by ASHRAE, 1997

Category:

Description

Reports a drop-in system performance comparison of refrigerants R22 and R407C. The test conditions include standard rating condition, overload condition and low-temperature condition. Finds that the cooling capacity of R407C is about 3% lower than that of the R22 system, and the coefficient of performance for the R407C system is 4% lower than that of the R22 system. The drop-in test results show that the condensing pressure for R407C is 200 to 300kPa higher than that of R22.

KEYWORDS: year 1997, Refrigerants testing, performance, comparing, R22, R407C, performance, coefficient of performance, heat transfer fluids, air conditioning

Citation: Symposium, ASHRAE Trans. 1997, vol.103, part 1